Westhomes Wcq2g ATS Automatic Transfer Switch 1p 2p 3p 4p

WCQ2G series MCB is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.

Social focus:

WCQ2G Moulded case circuit breaker

WCQ2G is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.

WCQ2G series double power supplies automatic transfer switch (ATS) applies to AC50Hz, rated operation voltage 400V, rated operation current 16A to 2000A, to two circuits power supply of emergency power supply system. It can be set as manual of the mutual transfer between frequent-use and backup power supply, as circuit controlling switch of control, signal, and interlock functions. Some types of the product have communication ports to make it realisable of remote control and unattended substation to the user. Itapplies to residence community, hospital, mall, airport, etc.,

The ATS meets standards IEC/EN60947 and GB/T14048.11.

Model and meaning

Working environment

The WCQ2G automatic transfer switch works reliably under the following conditions:
Altitude not exceeding 2000 meters
Ambient temperature not higher than 40℃,not lower than-5℃,relative humidity not more than 95%.
No explosion hazardous medium environment
No rain or snow attack environment

Note:If the switch is expected to be used in conditions where the ambient air temperatureis higher than+40℃or lower than -5~-45,the user should explain to the manufacturer.

KEY INFORMATION

WCQ2G

Pole  3P, 4P
Voltage  AC230V/400V
Icm 8KA-26KA
Inm(A) 100,160,250,630
In(A)  16-630

MAIN TECHNICAL DATA

Conventional thermal current Ith (A) 100 160 250 630 1600
Rated current In (A) 20 40 63 80 125 160 200 250 400 630 800 1000 1250 1600
Rated insulation voltage Ui (V) 690 690 690 690 690 690 690 690 690 690 690 690 690 690
Dielectric strength (V) 5000 5000 5000 5000 5000 5000 5000 5000 8000 8000 10000 10000 10000 10000
Rated impulse withstand voltage Uimp (kV) mounting catagory (IV) 8 8 8 8 8 8 8 8 12 12 12 12 12 12
Rated service current Ie (A) 400V AC-31 20 40 63 80 125 160 200 250 400 630 800 1000 1250 1600
AC-33 20 40 63 80 125 160 200 250 400 630 800 1000 1250 1600
AC-35 20 32 40 63 80 125 160 200 250 400 630 800 1000 1250
230V DC-31 20 40 63 80 125 160 200 250 400 630 800 1000 1250 1600
DC-33 20 40 63 80 125 160 200 250 400 630 800 1000 1250 1600
DC-35 20 32 40 63 80 125 160 200 250 400 630 800 1000 1250
Power of motor P (400V) (kW) 10 25 25 30 63 80 100 132 220 280 450 560 560 560
Rated short time withstand current Icw (kA Rms) 0.1S/1S 3/2.0 4/4.2 5/2.5 9/5 20/10 20/10 25/12 25/12 40/20 50/25 90/50 90/50 90/50 90/50
Rated breaking capacity (kA Rms) AC35 400V 160 320 500 640 1000 1000 1600 1600 3200 3200 8000 8000 8000 8000
Rated connecting capacity (kA Rms) AC35 400V 200 400 630 800 1250 1250 2000 2000 4000 4000 10000 10000 10000 10000
Rated short circuit breaking capacity Icm (kA peak value) 8 8 10 10 12 12 17 17 30 30 50 50 50 50
Mechanical life (circulation operation times) 100000 100000 100000 100000 100000 100000 100000 100000 5500 5500 4000 4000 4000 3000
Electrical life Cos Φ = 0.95 AC31 2500 2500 2500 1500 1500 1500 1500 1500 750 750 600 600 600 450
Cos Φ = 0.65 AC33 1500 1500 1500 1000 1000 1000 1000 1000 500 500 400 400 400 300
Cos Φ = 0.35 AC35 750 750 750 500 500 500 500 500 250 250 200 200 200 150
Transfer time I-O-II or II-O-I (s) 1.0 1.0 1.0 1.0 1.0 1.0 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.2
I-O or II-O-I (s) 0.5 0.5 0.5 0.6 0.6 0.6 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8
Motor energy consumption 24V (DC) (w) 40 40 40 75 75 75 75 75 90 90 120 120 120 120
230V (AC) (w) 40 40 40 75 75 75 75 75 90 90 120 120 120 120
Operation torque (Nm) 12 12 12 19 19 19 26 26 39 39 39 39 39 60
Weight (kg) Three poles 7.2 7.2 7.2 8 8 10 10 22 22 22 34
Four poles 4.2 4.3 4.4 7.5 7.5 7.5 9 9 11 11 28 28 28 40

OVERALL AND MOUNTING DIMENSION(MM)

FREQUENTLY ASKED QUESTION (FAQ)

What is an ATS and what does the Westhomes WCQ2G do? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

ATS stands for Automatic Transfer Switch. It automatically moves a load between two independent power sources—typically a utility (mains) supply and a generator or backup supply—without an operator. The WCQ2G is an integrated, motorized transfer switching device that continuously monitors both sources and transfers the load when the preferred supply fails.

What are the main features of the WCQ2G series? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The WCQ2G integrates the switch and logic control into one electromechanical unit, so no separate controller is required. It provides voltage detection, built-in electrical and mechanical interlocks, and supports automatic, motorized remote, and emergency manual operation. It also offers control, signal, and interlock functions, and some versions include communication ports.

How does automatic changeover work between the main supply and generator/backup? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

When the controller detects the mains voltage falling outside the set limits, it opens the main contact and transfers the load to the backup source. If the backup is a generator, the controller also sends a start signal and waits until the generator voltage and frequency are stable before transferring. When mains returns and stays stable through the retransfer delay, it switches back.

What do the 1P/2P/3P/4P pole options mean and how do I choose? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Poles count the number of conductors switched. 1P is for single-phase live-only, 2P switches live and neutral in a single-phase system, 3P switches the three phases in a three-phase three-wire system, and 4P switches three phases plus the neutral in a three-phase four-wire system. Choose 3P/4P for three-phase loads and 1P/2P for single-phase distribution.

What are the rated voltage and frequency? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The WCQ2G is designed for AC 50 Hz systems at a rated operational voltage of 400 V, with rated operational currents typically from 16 A up to the series maximum. The 400 V class matches common low-voltage three-phase distribution used in buildings, factories, and utility connections.

Does the WCQ2G provide a generator start signal? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Yes. The controller can output a relay contact signal to start the standby generator when mains failure is detected. It then waits for the generator output to reach a stable voltage and frequency window before transferring the load, and signals the generator to cool down and stop after retransfer.

What is the switching/transfer time? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The physical switching mechanism itself operates in a fraction of a second, while the full mains-to-generator sequence—detection, generator start, stabilization, and transfer—typically takes several seconds depending on the generator warm-up. Transfer delay and retransfer delay are adjustable on the controller to prevent unstable or rapid cycling.

What applications is the WCQ2G suited for? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It is used anywhere supply continuity matters, such as hospitals, data centers, commercial buildings, shopping malls, airports, factories, and residential communities. It is commonly applied at the main or sub-main distribution feeding critical or emergency loads.

Which standard does the WCQ2G comply with? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The WCQ2G meets IEC/EN 60947-6-1 (Transfer Switching Equipment) and the corresponding Chinese standard GB/T 14048.11. IEC 60947-6-1 covers transfer switching equipment rated up to 1000 V AC used to ensure continuity of supply and manage energy between sources.

How should I maintain and test the WCQ2G? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Perform periodic visual and mechanical inspection, check terminals for tightness, and exercise the mechanism through the manual or test transfer cycle. Verify that voltage sensing, generator start contacts, and interlocks function correctly, and confirm the set delays and thresholds. Keep the enclosure clean and dry, and record test results for compliance records.