New Design Wsb1-80 1p 40A 6ka 230V/400V/AC 6ka Mini Circuit Breaker

WSB1-80 series MCB is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.

Social focus:

WSB1-80 Moulded case circuit breaker

WSB1-80 series MCB is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.

Westhomes ACB and MCCB circuit breaker product series overview

WSB1-80 series MCBs are mainly applied at lines of AC 50Hz or 60Hz, rated operation voltage AC230/400V, rated current upto 80A, for overload and short circuit protection to the lines, also for changeover of infrequent operation to the lines. The MCBs are used at places of commercial office building, residential and similar building etc.

The product meets standards of GB 10963.1 and IEC 60898-1, at international advanced level.

Model and meaning

New Design Wsb1-80 1p 40A 6ka 230V/400V/AC 6ka Mini Circuit Breaker

KEY INFORMATION

WSB1-80

         Frequency  50Hz/60Hz
          Pole  1, 2, 3, 4
          Voltage  AC230V/400V
          kA  6kA, 10kA
          Amps  6, 10, 16, 20, 25, 32, 40, 50, 63,80
          Width  18, 36, 54, 72mm
          Mounting  Din rail
          Standard  IEC/EN 60898

Main technical parameters

Item No. WSB1-80
Rated current In(A) 6, 10, 16, 20, 25, 32, 40, 50, 63,80
Pole number 1P, 2P, 3P, 4P
Trip characteristics C type(5-10In); D type(10-20In)
Rated insulating voltage Ui(V) 690
Rated operating voltage Ue(V) AC230V/AC400V
Rated impulse voltage Uimp(kV) 4
Breaking capacity Icu(kA) 6
Mechanical life(times) 20000
Electrical life(times) 4000
No. Rated current Initial state Test current Time limit Expected result
1 In≤63 Cold state 1.13In t≤1h Not tripping
In>63 t≤2h
2 In≤63 Just followed the last test item 1.45In t<1h Tripping
In>63 t<2h
3 In≤32 Cold state 2.55In 1s Tripping
In>32 1s
4 Type C Cold state 5In t≤0.1s Not tripping
10In t<0.1s Tripping

OVERALL AND MOUNTING DIMENSION(MM)

Chinese Factory Price MCB Low Voltage Electrical Miniature Circuit Breaker

FREQUENTLY ASKED QUESTION (FAQ)

What is a 1P MCB and where is it normally used? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

A 1P (single-pole) MCB breaks only the live (phase) conductor of a single-phase branch circuit, leaving the neutral permanently connected. It is the standard protection device for individual lighting, socket-outlet, appliance and small-load branches in a consumer unit, and is the most space- and cost-effective way to protect individual circuits on a DIN rail.

Why is this particular model fixed at 40 A rather than selectable across a range? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The WSB1-80 series is offered in discrete standardized ratings (6, 10, 16, 20, 25, 32, 40, 50, 63, 80 A) and this SKU is factory-set to 40 A. The 40 A rating is a popular mid-size choice for 16 mm² or 10 mm² radial circuits, domestic electric showers up to about 9.2 kW, immersion heaters and commercial socket circuits on 6 mm² cable.

What does "6 kA breaking capacity" mean for a 40 A 1P breaker? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It means the breaker can safely clear a prospective short-circuit current of up to 6,000 A RMS at 230 V AC. This is sufficient for the vast majority of domestic and light-commercial final circuits in urban and suburban supply areas. If the board is fed directly from a very large transformer or very short, thick cables, calculate the PSCC — if it exceeds 6 kA, choose a 10 kA version instead.

How does the 1P WSB1-80 40 A actually trip on overload versus short circuit? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

A low-level overload (say 1.3 × 40 A) heats a bimetal strip inside the breaker, which bends over seconds or minutes and releases the mechanical latch — this is inverse-time thermal protection. A short circuit (e.g. 300 A) energizes a solenoid coil, whose armature snaps the mechanism open in milliseconds. The same contact set and arc chute extinguish both types of interruption.

Why is a 1P breaker rated "230V/400V AC" when it only switches one pole to neutral? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The 230 V is the working voltage across the single pole to neutral; the 400 V figure is the rated insulation and arc-withstand voltage between the poles and to earth, which lets the breaker be mounted in a 400 V three-phase board alongside 2P/3P/4P breakers without compromising clearances. Practically, you connect it between one phase and neutral on a 230 V supply.

Which tripping curve is standard for a 40 A 1P branch, B or C? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

For a purely resistive 40 A load (shower, immersion, heater), a B-curve breaker (3–5 In magnetic trip) is typical. For a 40 A mixed socket-outlet or small motor circuit, C-curve (5–10 In) is preferred to avoid nuisance tripping from motor start-up or capacitor inrush. D-curve is rarely needed on a 1P 40 A domestic branch unless the load is a dedicated transformer or high-inrush device.

How do I wire line and load on a 1P 40 A WSB1-80? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Feed the phase conductor from the busbar or supply into the top (line) terminal marked "L" or "IN". Run the phase going to the branch circuit from the bottom (load) terminal. Neutral is not connected to the breaker — it must land on the neutral bar. Tighten the terminal screw to the torque value printed on the side of the breaker (typically 1.8–2.5 N·m) to avoid overheating.

What cable size should I pair with a 40 A 1P MCB? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Under typical IEC 60364 conditions, a 6 mm² copper cable clipped direct can carry about 40 A, so 6 mm² is the minimum for a 40 A circuit; if the cable is enclosed in insulation, runs long distances or is grouped with other cables, step up to 10 mm². Always verify the cable's Iz (current-carrying capacity under actual installation conditions) is at least 40 A, and check voltage drop over the run.

Why does my 40 A 1P MCB keep tripping — is it defective? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Start with the usual causes before replacing it: (1) the load genuinely exceeds 40 A — check the combined current of everything on the circuit; (2) a motor, compressor or transformer on the circuit has high inrush that trips a B-curve breaker — switch to C or D; (3) a developing insulation fault or appliance fault causes intermittent overcurrent; (4) loose terminals are heating the bimetal; (5) repeated short-circuit trips have weakened the mechanism. A properly rated MCB should never trip on normal running current.

Is this 1P 40 A MCB DIN-rail mountable and compliant with IEC 60898-1? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Yes. It snaps onto a standard 35 mm DIN rail (EN 60715) inside a consumer unit or distribution enclosure, and the WSB1-80 series is designed, type-tested and CE-marked in accordance with IEC 60898-1. That guarantees consistent thermal and magnetic trip times, correct contact gap and short-circuit endurance so it can be substituted directly for other compliant 40 A 6 kA 1P MCBs on the market.