WR2L-63 1P+N 63A Single-Phase Residual Current Circuit Breaker

Discover the Westhomes WR2L-63 1P+N RCCB, a 63A Residual Current Circuit Breaker with shock and fire protection options for your safety.

Social focus:

WR2L-63 1P+N RCCB 63A Residual Current Circuit Breaker | AC/A Type

Westhomes WR2L-63 1P+N RCCB – Advanced Earth Leakage Protection with High Fault Tolerance.

The Westhomes WR2L-63 Series Residual Current Circuit Breaker (RCCB) is engineered to provide superior protection against earth leakage currents and indirect contact risks. Designed for both residential and industrial applications, this 1P+N device combines high breaking capacity with flexible sensitivity options to ensure maximum safety for personnel and equipment.

Key Features:

1P+N Compact Design: Switches both phase and neutral simultaneously while detecting residual currents, ensuring complete circuit isolation during fault conditions.

Precise Tripping Characteristics: Engineered for accurate and reliable tripping at the specified residual current levels, minimizing nuisance tripping.

Premium Build Quality: Manufactured to higher specifications for increased durability, better contact resistance, and longer operational life.

User-Friendly Design: Features a clear status indicator and ample wiring space for easy installation and maintenance.

Protective Functions:

Earth Leakage Protection

Personal Shock Protection

Neutral-Phase Reverse Connection Protection

Contact Indication & Status Monitoring

Applications:

High-End Residential

Medical Facilities

Commercial & Light Industrial

KEY INFORMATION

Standard IEC/EN61008-1
Protection Ground fault
Type of trip Electro-magnetic
Type of protection(electric leakage) AC,A,B,G,S
No.of poles 2P(1P+N),4P(3P+N)
Rated current In 6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤40A),10In(In>40A)
Rated voltage Ue 1P+N:230/240V~,3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 6KA
SCPD fuse 600,010,000
Rated impulse withstands voltage(1.5/50)Uimp 4,000V
Dielectric test voltage at ind.Freq.for 1min 2kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
Contact position indicator Yes
Protection degree IP20
Ambient temperature -25℃ to+55℃,Max.95%humidity
Terminal connection type Cable/Pin-type busbar/Fork-type busbar/U-type busbar
Max.terminal size for cable 50mm²
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top and bottom
Protection Ground fault
Type of trip Electro-magnetic
Type of protection(electric leakage) AC,A,B,G,S
No.of poles 2P(1P+N),4P(3P+N)
Rated current In 6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤40A),10In(In>40A)
Rated voltage Ue 1P+N:230/240V~,3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 6KA
SCPD fuse 600,010,000
Rated impulse withstands voltage(1.5/50)Uimp 4,000V
Dielectric test voltage at ind.Freq.for 1min 2kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
Contact position indicator Yes
Protection degree IP20
Ambient temperature -25℃ to+55℃,Max.95%humidity
Terminal connection type Cable/Pin-type busbar/Fork-type busbar/U-type busbar
Max.terminal size for cable 50mm²
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top and bottom

Packaging and delivery

Selling Units Single item

Lead time

Quantity (pieces) 1 – 1,000 > 1,000
Lead time (days) 15 To be negotiated

Key attributes

Type MCB, AC MCB, RCCB
BCD Curve C
Rated Frequency (Hz) 50hz/60hz
Material Copper
Application Circuit-Breaking, Industrial, Households, Protection, Electric Power
Model Number WR1L-63
Rated Voltage 220V/230V
Breaking Capacity 6 kA
Mounting Type Rail Mounting
Protection LSI
Place of Origin Zhejiang, China
Brand Name Westhomes

FREQUENTLY ASKED QUESTION (FAQ)

What is a 1P+N single-phase RCCB? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It is a residual current circuit breaker for single-phase 230V circuits, with one switched phase pole and one switched neutral pole, both monitored by an internal toroidal CT. It provides protection against electric shock and earth leakage, but — like all RCCBs — no protection against overload or short circuit, which must be supplied by an upstream MCB.

How does it detect leakage current? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Live (L) and neutral (N) pass through a ring-shaped current transformer. When no leakage exists, the outgoing current on L equals the returning current on N and the magnetic fields cancel. When current leaks to earth through insulation failure, a wet appliance, or a person touching a live part, the two currents no longer balance; the CT detects the residual flux, the trip solenoid fires, and the contacts open almost instantaneously.

What does "1P+N" mean vs "2P"? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

"1P+N" indicates one protected/switched phase pole plus a switched neutral pole, but only the phase pole has overcurrent-related mechanical rating structure; the neutral pole is opened in step with the phase. A true "2P" RCCB treats both poles symmetrically. For most single-phase residential sub-mains, 1P+N is the standard, compact form factor.

What is the 63A rating used for? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

63A is the maximum continuous current the unit can carry at 230V, 50/60 Hz, without overheating. It is typically chosen for single-phase sub-main distribution boards, large socket-outlet groups, or feeds to a sub-panel. The downstream MCBs are chosen to match the actual cable size and load, not the RCCB's 63A rating.

What residual sensitivity is recommended? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

30 mA (IΔn) is the universal standard for additional shock protection in residential and general-purpose circuits. It trips fast enough to protect a person under normal touch-voltage conditions. Use 10 mA in bathrooms, near swimming pools, or for outdoor circuits, and 100–300 mA upstream only for fire protection or equipment monitoring, never as the sole human-protection device.

Type AC vs Type A — which is right for modern homes? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Type AC detects only sinusoidal AC leakage. Type A detects AC plus pulsating DC leakage, which appears when devices with rectifier stages (TVs, computers, LED drivers, inverter washers, EV chargers) develop an earth fault. Most wiring rules now favor Type A for new single-phase installations because of the prevalence of electronic loads; Type AC is acceptable only on purely resistive, traditional circuits.

How do I wire it in a single-phase board? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Connect the incoming phase to L (IN) and incoming neutral to N (IN); run load phase and load neutral from the OUT terminals to downstream MCBs. The protective earth (PE) wire runs straight to the earth bar and must not pass through the device. Observe the marked L and N polarity on the label; reversing them can prevent correct operation on electronic-type devices.

How does it differ from an RCBO? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

An RCCB trips only on residual (earth leakage) current. An RCBO (Residual Current Breaker with Overcurrent) combines the same leakage sensing with a thermal-magnetic MCB in one unit, so it also trips on overload and short circuit. If you need per-circuit protection with only one device per circuit, use an RCBO; if you want one common RCCB upstream of several MCBs, use a 1P+N RCCB.

What about DIN rail mounting and testing? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It snaps onto a 35 mm DIN rail and typically occupies 2 pole-widths. With the circuit energized, press the "T" test button once a month; it should trip immediately. If it does not trip, the device is faulty and must be replaced, because it provides no protection even though power remains on. Reset by moving the handle fully to OFF and then ON.

Which standards and certifications apply? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It is built to IEC 61008-1 (RCCB without integral overcurrent protection for household and similar uses), rated up to 440V AC. CE marking confirms conformity with the Low Voltage and EMC Directives. Always confirm the declared rated residual operating current (IΔn), the Type (AC/A), and the breaking/tripping characteristic in the datasheet, and keep the certificate available for inspection.