WCM9Z Moulded case circuit breaker
WCM9Z is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.
Get quick appointment for technical support!
WCM9Z series MCB is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.
WCM9Z is one of updated type MCCBs researched and developed by the company by using advanced design and manufacture technology internationally.

WCM6 sereis moulded case circuit breaker (MCCB for short) is the new type of product with top current limiting principal and manufacture technology in design, is tight in structure, total molularized, high breaking capacity, zero flashover. It applies at AC50Hz, rated operation voltage 690V and below, rated operation current upto 1250A for infrequent switch of line and infrequent start of motor. MCCB has overload, short circuit and under voltage protection device, to protect line and power evice from demage.
| Pole | 2P, 3P |
| Voltage | DC 1000V/1250V/1500V |
| kA | Ue1000v 20kA, Ue1500v 15kA |
| Inm(A) | 250A, 630A |
| In(A) | 100/125/140/160/180/200/225/250/320/350/400/500/630A |
| Model | WCM9Z | WCM9Z | WCM9Z | |
| Rated operating voltage(Ue) | DC1000V | DC1250V DC1500V | DC1000V DC1250V DC1500V | |
| Rated insulation voltage (Ui) | 1500V | 1500V | 1500V | |
| Rated impulse voltage (Uimp) | 12kV | 12kV | 12kV | |
| Number of poles | 2 | 3 | 4 | |
| Trip unit type | Thermomagnetic type (thermal magnet is not adjustable) TMD Fixed | |||
| Frame rated current (Inm) | 250A | 630A | ||
| Rated operating current (In) | 100/125/140/160/180/200/225/250A | 320/350/400/500/630A | ||
| Rated ultimate short circuit breaking capacity (lcu) | Ue1000v 20kA | Ue1500v 15kA, Ue1250v 20kA | Ue1250/1500v 15kA, Ue1000v 20kA | |
| Operational breaking capacity (Ics) | 75%ICU | Ue1500v 15kA, Ue1250v 20kA | Ue1250/1500v 15kA, Ue1000v 20kA | |
| Protective function | Long time delay protection (Ir) | 1In | ||
| Instant protection (li) | 6In(Min1000A) | |||
| Service life | Mechanical | 10000times | 5000times | |
| Electrical | 1000times | 500times | ||
| Installation type | Fixed | Fixed | Fixed | |
| Protection level | Wiring port: IP20/All sides: IP40 | |||
| Operating temperature | -40ºC~+75ºC | |||
| Operating Instructions | ON/OFF instruction | |||
| Is the release adjustable? | NO | |||
| Isolation function | YES | |||
An intelligent molded case circuit breaker (MCCB) uses a microprocessor-based electronic trip unit instead of a simple thermal-magnetic mechanism to detect and clear faults. In addition to basic overload and short-circuit protection, it typically offers programmable protection curves, real-time metering, on-board display, remote communication, and event recording. This makes it suitable for smart distribution systems where visibility and coordination matter as much as protection itself.
An electronic trip unit samples current through current transformers or Rogowski coils and evaluates the signal in a microcontroller against pre-programmed I²t curves, typically achieving ±5% trip accuracy and being nearly insensitive to ambient temperature. A thermal-magnetic unit relies on a heated bimetal strip for overload and a magnetic coil for short circuits, with typical accuracy of ±10–15% and noticeable temperature drift. The electronic version costs more up front but offers programmable curves, tighter selectivity, and built-in metering and communication.
The 250A and 630A refer to the frame size (maximum continuous current) of the WCM9Z breaker. The 250A frame typically covers In settings from roughly 125A to 250A, while the 630A frame covers from about 400A to 630A. You select the frame based on the maximum expected load current and downstream cable sizing, then set the actual trip rating (Ir) to match the connected load after temperature and altitude derating. Choosing a frame larger than the minimum required also leaves room for future load growth.
LSI stands for Long-time, Short-time, and Instantaneous protection stages. The long-time pickup (Ir) and delay (tr) handle sustained overloads with an inverse-time curve; the short-time pickup (Isd) and delay (tsd) provide time-delayed short-circuit coordination so downstream breakers trip first; the instantaneous pickup (Ii) clears bolted faults immediately. On the WCM9Z intelligent model these values are adjustable via the front display, a programming keypad, or remotely over Modbus, allowing engineers to build fully selective protection schemes.
Yes, the WCM9Z intelligent electronic trip unit supports earth-fault (ground-fault) protection as an extended LSIG function. It measures residual current through a neutral or toroidal sensor and trips at an adjustable pickup threshold with a selectable time delay. This is essential for systems where dangerous ground-fault currents must be detected faster and more accurately than a standard overload or instantaneous element can provide.
The intelligent WCM9Z includes an LCD or LED front display that shows real-time measurements such as three-phase current, voltage, active/reactive/apparent power, power factor, and accumulated energy consumption. Some configurations also display demand current, temperature, and pre-alarm status. This on-board metering removes the need for separate panel meters and gives operators immediate visibility into load health without opening the panel door.
Yes, the WCM9Z intelligent model is equipped with an RS485 communication port supporting the Modbus-RTU protocol. This allows the breaker to be integrated into a SCADA, BMS, or energy management system for remote monitoring of current, power, and energy values, as well as remote signaling of breaker status and fault events. A single twisted-pair RS485 bus can daisy-chain multiple breakers on one line for cost-effective networked distribution.
The WCM9Z intelligent unit records trip events with timestamp, type of fault (overload, short circuit, earth fault, under/over voltage), and peak fault current, typically storing the last several dozen events in non-volatile memory. It also provides pre-alarm warnings for overload approaching pickup, high neutral current, or over-temperature conditions, signaled via front LEDs, relay outputs, or bus messages. This event history is invaluable for root-cause analysis after a nuisance trip or downstream fault.
Yes, Westhomes offers ODM and OEM customization for the WCM9Z series, including custom logo and labeling, tailored trip curve configurations, optional communication modules (Modbus, Profibus, etc.), auxiliary contact and shunt trip combinations, and packaging or branding to match the customer's product line. The 250A and 630A frames give panel builders a flexible platform for private-label switchgear and distribution boards.
The intelligent WCM9Z adds a microprocessor trip unit, adjustable LSI/LSIG protection curves, a digital display, metering, Modbus communication, and event logging, making it ideal for smart distribution, data centers, and industrial plants requiring selectivity and remote monitoring. The manual WCM9Z uses a conventional thermal-magnetic trip unit with simpler (or fixed) settings, no display or communication, and a lower upfront cost. Choose the intelligent version when coordination accuracy, metering, or networked monitoring is required; choose the manual type for straightforward, cost-sensitive feeders where those features are unnecessary.