WR1L-63 1P+N 63A Residual Current Circuit Breaker with Neutral Protection

Protect single-phase circuits with Westhomes’ WR1L-63 1P+N RCCB. 63A rating, 30-300mA adjustable leakage protection for reliable safety.

Social focus:

WR1L-63 1P+N 63A Residual Current Circuit Breaker with Neutral Protection | AC/Type A

Westhomes WR1L-63 1P+N RCCB – Compact Earth Leakage Protection for Single-Phase Circuits.

The Westhomes WR1L-63 Series 1P+N Residual Current Circuit Breaker (RCCB) delivers reliable protection against earth leakage currents in residential, commercial, and light industrial applications. This compact device combines high breaking capacity with flexible sensitivity options to ensure maximum safety for both personnel and equipment in single-phase installations.

Key Features:

Multiple Sensitivity Ratings: Available in 30mA (personal protection), 100mA (fire protection), and 300mA (equipment protection) to match specific safety requirements.

Compact 1P+N Design: Space-saving single-module width design, ideal for use in standard distribution boards where space is at a premium.

Wide Voltage Compatibility: Supports up to 400V AC systems, providing flexibility for various installation types worldwide.

Dual-Purpose Application: Industrial-grade durability combined with safety features suitable for household use.

Protective Functions:

Earth Leakage Protection

Combined Phase + Neutral Switching

Indirect Contact Protection

Applications:

Residential distribution boards

Commercial socket outlet circuits

Small office power distribution

Circuits with electronic loads

KEY INFORMATION

Standard IEC/EN61008-1
Protection Ground fault
Type of trip Electro-magnetic
Type of protection(electric leakage) AC,A,B,G,S
No.of poles 2P(1P+N),4P(3P+N)
Rated current In 6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤40A),10In(In>40A)
Rated voltage Ue 1P+N:230/240V~,3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 6KA
SCPD fuse 600,010,000
Rated impulse withstands voltage(1.5/50)Uimp 4,000V
Dielectric test voltage at ind.Freq.for 1min 2kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
Contact position indicator Yes
Protection degree IP20
Ambient temperature -25℃ to+55℃,Max.95%humidity
Terminal connection type Cable/Pin-type busbar/Fork-type busbar/U-type busbar
Max.terminal size for cable 50mm²
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top and bottom
Protection Ground fault
Type of trip Electro-magnetic
Type of protection(electric leakage) AC,A,B,G,S
No.of poles 2P(1P+N),4P(3P+N)
Rated current In 6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n 10,30,100,300mA
Residual current off-time under I△n ≤0.1s
Rated residual making and breaking capacity(I△m) 500A(In≤40A),10In(In>40A)
Rated voltage Ue 1P+N:230/240V~,3P+N:400/415V~
Rated frequency 50/60Hz
Rated breaking capacity 6KA
SCPD fuse 600,010,000
Rated impulse withstands voltage(1.5/50)Uimp 4,000V
Dielectric test voltage at ind.Freq.for 1min 2kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
Contact position indicator Yes
Protection degree IP20
Ambient temperature -25℃ to+55℃,Max.95%humidity
Terminal connection type Cable/Pin-type busbar/Fork-type busbar/U-type busbar
Max.terminal size for cable 50mm²
Max. tightening torque 2.5N.m
Installation Mounting on 35mm DIN rail
Connection From top and bottom

Packaging and delivery

Selling Units Single item

Lead time

Quantity (pieces) 1 – 1,000 > 1,000
Lead time (days) 15 To be negotiated

Key attributes

Type MCB, AC MCB, RCCB
BCD Curve C
Rated Frequency (Hz) 50hz/60hz
Material Copper
Application Circuit-Breaking, Industrial, Households, Protection, Electric Power
Model Number WR1L-63
Rated Voltage 220V/230V
Breaking Capacity 6 kA
Mounting Type Rail Mounting
Protection LSI
Place of Origin Zhejiang, China
Brand Name Westhomes

FREQUENTLY ASKED QUESTION (FAQ)

What does "1P+N with Neutral Protection" mean? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

In a 1P+N RCCB, the single phase conductor (L) is switched and monitored, and the neutral conductor (N) passes through the toroid. "Neutral protection" means the neutral pole is opened together with the phase when the device trips, so the load is fully isolated from both conductors rather than leaving neutral connected. This is important because a live neutral-to-earth fault can still present a shock hazard.

How does this RCCB detect leakage? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Both L and N pass through the same toroidal (zero-sequence) current transformer. Under healthy conditions the current on L equals the current returning on N, so their magnetic fields cancel and no flux is detected. When insulation fails or a person touches a live part, part of the current returns via earth instead of neutral; the toroid senses this imbalance, the trip relay operates, and the contacts open within a fraction of a second.

Why is the 63A rating relevant in a 1P+N single-phase circuit? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

63A is the continuous current rating of the device per pole, sized for the largest single-phase sub-main circuits in a home or small commercial panel. It does not trip on overload — pair it with an MCB or fuse sized to the cable (e.g., a 40A or 50A MCB for the actual load). The 63A rating simply says the RCCB itself can carry that current without overheating.

What residual sensitivity should I expect? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The standard residential residual sensitivity is 30 mA (IΔn). At 30 mA the device provides additional protection against direct contact for people. For circuits in bathrooms, swimming pools, or wet locations, a 10 mA unit is often required; for protection against fire on large cable networks, 300 mA types are used upstream.

How is a 1P+N RCCB wired? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Connect the incoming phase to the terminal marked L (IN) and the incoming neutral to N (IN). Run the load phase and load neutral from the OUT terminals to the downstream branch circuits. The protective earth (PE) wire must never pass through the device or be connected to its terminals. Note the polarity marked on the unit — reversing L and N on some electronic types can prevent correct operation.

What is the difference between this and a 4P RCCB? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

The 4P version is built for three-phase four-wire (3×L+N) circuits and monitors the sum of all four conductors; the 1P+N version is built for single-phase (L+N) 230V circuits and has one phase plus one neutral pole. Use 1P+N on single-phase sub-mains, socket-outlet groups, and individual appliances; use 4P only on three-phase incomers or three-phase loads.

Type AC vs Type A — which one do I need? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Type AC responds to pure sinusoidal AC leakage only. Type A responds to AC plus pulsating DC residual currents, which is essential when the load includes switch-mode power supplies, LED drivers, washing-machine inverter boards, or EV chargers. Modern residential loads increasingly contain electronics, so Type A is usually the safer and code-compliant choice; pure Type AC is being phased out in many markets for new installations.

Does it protect against overload and short circuit? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

No. An RCCB trips only on residual (earth leakage) current. It will not protect the cables from overheating under overload, nor from a line-to-neutral short circuit. Install an MCB upstream or on the same rail (or choose an RCBO, which combines both functions in one unit) for overcurrent and short-circuit protection.

How do I mount and maintain it? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

Clip it onto a 35 mm DIN rail in the distribution box, tighten conductors to the nameplate torque, and route incoming and outgoing wires cleanly. Press the "T" test button once a month to confirm tripping; if it fails to trip, replace the unit. Every one to two years, an electrician should inspect terminal tightness and check for damp, dust, or rodent damage inside the enclosure.

Which standard and certifications apply? plus-square Created with Sketch Beta. minus-square Created with Sketch Beta.

It is designed to IEC 61008-1 (RCCB without integral overcurrent protection for household and similar uses), rated up to 440V AC. CE marking confirms compliance with the applicable European directives. Verify the IΔn value, Type (AC/A), and the number of poles against the installation design, and ensure the certificate/copy of the test report is available for the local electrical inspector.